TU840 Communication Module

TU840 Communication Module

The ABB TU840 has a rotary switch for cluster address setting, mechanical keying prevents insertion of wrong module type, double Module Bus connection and latching device to DIN rail for locking and grounding DIN rail mounted.
Brand: ABB
Place of origin: Sweden
Delivery: 8 to 10 weeks
Chat Now

Product Details

1.    General Introduction

The TU840 is a module termination unit (MTU) for redundant configuration of Optical Module Bus Modem TB840/TB840A.

The MTU is a passive unit having connections for power supply, double electrical Module Bus, two TB840/TB840A and a rotary switch for cluster address (1 to 7) setting.

Four mechanical keys, two for each position, are used to configure the MTU for the right types of modules. Each key has six positions, which gives a total number of 36 different configurations. The configurations can be changed with a screwdriver.

Termination Unit TU840 connects TB840/TB840A to redundant I/O. Termination Unit TU841 connects TB840/TB840A to non-redundant I/O.


2.    Specification of TU840

General info

Type

ABB's   Module bus

Article   number

3BSE020846R1

Master   or slave

Not   Applicable

Line   redundancy

Yes

Module   redundancy

Yes

Hot   Swap

No

Type

Redundant   TB840/TB840A, Redundant I/O, Single Power

Power   input

24   V d.c. (19.2 - 30 V)

Mounting

Vertical   or Horizontal

Detailed data

Connector

N/A

24   V consumption typ.

N/A

Module   Bus current distribution

Maximum   5V 1.5 A

24V   1.5 A

Mechanical Keys

36   different combinations

Acceptable wire sizes

Solid:   0.2 - 2.5 mm2

Stranded:   0.2 -2.5 mm2, 24 -12 AWG

Recommended   torque: 0.5 Nm

Rated insulation voltage

50   V

Dialectic test voltage

500   V a.c.

Power dissipation

2.0W

Environmental and certification

Temperature,   Operating

55°   C (131° F) horizontal mounted. 40° C (104° F) vertical mounted

Temperature,   Storage

-25°   C (-13° F) to +70° C (158° F)

Equipment   class

Class   I according to IEC 60536; (earth protected)

Ingress   protection

IP20   according to IEC 60529

CE-   marking

Yes

Electrical   Safety

cULus

Hazardous   Location

cULus   Hazardous Location Class 1 Zone 2, ATEX Zone 2

Marine   certificates

ABS,   BV, DNV-GL, LR, RS

RoHS   compliance

DIRECTIVE/2011/65/EU   (EN 50581:2012)

WEEE   compliance

DIRECTIVE/2012/19/EU

Dimensions

Width

124   mm (4.88 in.)

Depth

47   mm (1.85 in.)

Height

186   mm (7.32 in.) including latch

Weight   (including base)

0.45   kg (0.99 lbs.)


3.    Selection table of S800I/O Communication Modules

Name

Line redundancy

Master or slave

Module redundancy

Protocol

CI801

No

Slave

No

PROFIBUS DP-V1

CI840A

Yes

Slave

Yes

PROFIBUS DP-V1

CI845

Yes

Slave

Yes

N/A

TB820V2

No

Slave

No

ABB's Module bus

TB825(Multi Mode)

No

Slave

No

ABB's Module bus

TB826(Single Mode)

No

Slave

No

ABB's Module bus

TB840

Yes

Slave

Yes

ABB's Module bus

TB842

Yes

Slave

Yes

ABB's Module bus

TC810

Yes

-

Yes

N/A

TU807

-

Not Applicable

-

ABB's Module bus

TU840

Yes

Not Applicable

Yes

ABB's Module bus

TU841

Yes

Not Applicable


ABB's Module bus

TU846

Yes

Not Applicable

Yes

PROFIBUS DP-V1

TU847


Not Applicable

Yes

PROFIBUS DP-V1

TU848

Yes

Not Applicable

Yes

ABB's Module bus

TU849

Yes

Not Applicable

-

ABB's Module bus

TU860

-

-

-

N/A

 


Hot Tags: tu840 communication module, Dubai of UAE, ABB, suppliers, price, quotation, contractor, revamping, engineering, upgrading, installation, commissioning, immigration, integrator, configuration, programming